Download Print this page

Akytec MU210-401 Short Manual

Digital output module
Hide thumbs Also See for MU210-401:

Advertisement

Quick Links

Digital output module
Short guide
1. Overview
MU210-401 is an extension module with 8 relay outputs.
The module operates as a slave in Ethernet network with Modbus TCP
protocol.
The device is intended for use in industrial automation for creation of
decentralized control systems.
2. Environmental conditions
Table 1 Operating conditions
Permissible range
Condition
Ambient temperature
Transportation and storage
Relative humidity
up to 95 % (at +35 °C, non-condencing)
up to 2000 m ASL
Attitude
IP code
Vibration / shock resistance
conforms to IEC 61131-2
EMC emission / immunity
conforms to IEC 61131-2
3. Specification
Table 2 General specifications
Parameter
Electrical
Power supply
Power consumption
Polarity protection
Appliance class
Interfaces
Double Ethernet 10/100 Mbps
Data transfer
Protocols
Configuration interface
Digital outputs
Outputs number
Output type
Control
AC
5 A, 250 VAC, resistive load
Switching capacity
DC
Switching current, min.
Switching time
PWM frequency, max.
PWM pulse length, min.
Optional functions
3 A, 30 VDC
Service life, electrical
5 A, 250 VAC
Service life, mechanical
5,000,000 switching cycles
MU210-401_3-EN-44016-2.1
© All rights reserved. Subject to technical changes and misprints.
File size, max.
Number of log files, ,max.
Logging interval, min.
Accuracy
Backup battery
Dimensions
Weight
4. Installation and connection
Before installation make sure there is enough free space for connecting
-40...+55 °C
the module and placing the wires. The module is mounted on a DIN rail
or on a vertical surface using screws.
Installation of external connections is carried out by a wire with a cross
section of not more than 0.75 mm
IP20
For stranded wires, use end sleeves.
After installation, put the wires into the cable channel of the module
housing and close the cover.
If necessary, in order to remove the terminal blocks of the module, loosen
the two screws at the corners of the terminal blocks.
Value
CAUTION
Connection and maintenance is performed only when the
24 (10 ... 48) V DC
module power and the power to all devices connected to it is
6 W at 24 V DC
turned off.
Yes
Table 3 Network parameters
II
Parameter
IP address
Modbus TCP
Subnet mask
MQTT
Gateway
SNMP
DNS server 1
NTP
USB 2.0 (MicroUSB)
DNS server 2
Ethernet 10/100 Mbps
5. Connection diagrams
8
Relay, NO
On-Off or PWM
3 A, 30 VDC
10 mA at 5 VDC
15 ms
1 Hz with 0.05 duty cycle
50 ms
Safe state
35,000 switching cycles
50,000 switching cycles
MU210-401
Digital output module
Parameter
Value
Flash-memory (log file storage)
2 kB
1000
10 s
Real time clock
±3 s/day at +25 °С
±10 s/day at -40 °С
CR2032
Mechanical
42 × 124 × 83 mm
approx. 260 g
2
.
Description
Default value
IPv4 Internet Protocol address
192.168.1.99
IP address recognition area in the
255.255.255.0
subnet
IP address of the gateway
192.168.1.1
Primary DNS server
77.88.8.8
Secondary DNS server
Fig. 1 Device connectors
Fig. 2 Front view (open cover)
Table 4
Terminal assignments
Marking
NC
Not connected
DO 1,2A
Common terminal A for outputs 1,2
DO3A...DO8A,
Output terminal
DO1B...DO8B
NOTE
It is not allowed to connect wires to NC contacts.
8.88.8.8
The service button performs the following functions:
• Factory settings restore
• IP-address assignment
Fig. 3 Relay output wiring
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Description
Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de

Advertisement

loading
Need help?

Need help?

Do you have a question about the MU210-401 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MU210-401

  • Page 1 Fig. 1 Device connectors Service life, mechanical 5,000,000 switching cycles MU210-401_3-EN-44016-2.1 akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany © All rights reserved. Subject to technical changes and misprints. Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de...
  • Page 2 Digital output module 6. Settings The module is configured via the Modbus TCP protocol or in the akYtec Tool Pro program via the USB interface (see User Guide). If the module is connected to the USB port, the main module power supply is not required.