Maintenance
The setting should be kept as high as acceptable to increase the lifetime of the actuator.
Daylight (daylight saving time changeover)
Choose whether you want the change to summer / winter time to be automatic or manual.
ON:
The controller's built-in clock automatically changes + / - one hour on
the standardized days for daylight saving time changeover for Central
Europe.
You change manually between summer and winter time by setting the
OFF:
clock backward or forward.
ECL address (master / slave address)
This settting is relevant if more controllers are working in the same ECL Comfort system (connected via
the ECL BUS) and / or ECA units are connected.
0:
The controller works as slave. The slave receives information about the
outdoor temperature (S1), system time, and signal for DHW demand
from the master.
The controller works as slave. The slave receives information about the
1 ... 9:
outdoor temperature (S1), system time, and signal for DHW demand
from the master. The slave sends information about the desired flow
temperature to the master.
10 ... 14: Not used.
The controller is master.
15:
The ECL Comfort controllers can be connected via the ECL BUS to perform a larger
system.
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to receive information
about outdoor temperature and system time.
AQ188586469032en-010701
Setting range
ON / OFF
Setting range
0 ... 15
7198
Factory setting
ON
7199
Factory setting
15