7 TESTING AND TROUBLESHOOTING
Table 7–2: PROGRAMMING EXAMPLE (Sheet 4 of 4)
KEYPRESS
DISPLAY
,
REG PF:
SCROLL to change
REG GAIN:
ENTER to modify
STABILITY: 1 cyc
ENTER to modify
,
REG OUTPUT: 5 V
ENTER to modify
,
REG OUTPUT: 10 V
SCROLL to change
,
FLOOR VOLTS: 0.00
ENTER to modify
,
FLOOR VOLTS: 5.00
SCROLL to change
GE Multilin
Courtesy of store.ips.us
0.85
10
SETPOINTS?
ENTER for menus
SAVE CHANGES?
ENTER to save...
PROGRAMMING MODE
SCROLL PASSWORD
TEST MODE
SCROLL for tests
Coll-Ring Motor
SPM READY
SPM Synchronous Motor Protection and Control
COMMENTS
Change the existing value of REG PF to 0.85 leading. SCROLL
Key(s) to select value of 0.85 and then SELECT/ENTER key to
accept new value
SCROLL DOWN key to move to REG GAIN setpoint. This setpoint
is correct
SCROLL DOWN key to move to STABILITY setpoint. This
setpoint is correct
SCROLL DOWN key to move to REG OUTPUT setpoint then
SELECT/ENTER to select the setpoint.
Change the existing value of REG PF to 10V. SCROLL Key(s) to
select value of 10 and then SELECT/ENTER key to accept new
value
SCROLL DOWN key to move to FLOOR VOLTS setpoint then
SELECT/ENTER to select the setpoint.
Change the existing value of FLOOR VOLTS to 5.00. SCROLL
Key(s) to select value of 5.00 and then SELECT/ENTER key to
accept new value
Exit out to SETPOINTS menu.
Save setpoint changes.
Exit out to PROGRAMMING MODE menu
Exit out to TEST MODE menu
Ready-mode display
7.5 PROGRAMMING
7-
11
7