5 SETPOINTS
EX VLT DLY: 0.3 s
ENTER to modify
FUNCTION:
The exciter voltage delay setpoint is the time delay that will elapse after the exciter voltage falls below the pro-
grammed setpoint before the SPM initiates tripping action for field undervoltage (CHECK EXCITER)
MOTOR TYPE:
Collector-Ring or Brushless
NOTE:
The EXCITER VOLTS option must be enable before this feature can be used.
INC SEQ DLY:
ENTER to modify
INC SEQ DLY:
ENTER to modify
FUNCTION:
If the SPM does not properly complete its starting sequence in the setpoint time, the SPM will trip and display
an in-complete sequence condition.
COLLECTOR-RING: The time setting may be set to a value between 1 and 100 seconds, but not less than the
FCX delay setpoint.
BRUSHLESS: The time setting may be set to a value between 1 and 200 seconds, but not less than the sum of
the FAR delay setpoint and the FCX delay setpoint.
MOTOR TYPE:
Collector-Ring or Brushless
GE Multilin
Courtesy of store.ips.us
Range: 0.3 to 5.0 seconds
Step: 0.1 second
OFF
Collector-Ring
Range: 1 to 100 seconds, OFF
Step 1
OFF
Brushless
Range: 1 to 200 seconds, OFF
Step 1
SPM Synchronous Motor Protection and Control
5.2 SETPOINTS MENU

5.2.18 FIELD UNDERVOLTAGE DELAY

5.2.19 INCOMPLETE SEQUENCE DELAY