Configuration Of A Pressure Or A Temperature Probe Type At X61 Door; Configuration Of A Pressure Or A Temperature Probe Signal At X61 Door; Configuration Of The X62 Door Input Signal - Unigas HTP2000 Installation Manual

Table of Contents

Advertisement

6.2

Configuration of a pressure or a temperature probe type at X61 door

ATTENTION: If the external load controller is set do not connected to terminals X60 or X61.
If a modulation probe is connected to the X61 terminal, proceeding as follows:
1st level
2nd level
Params & Display
LoadController
6.2.1

Configuration of a pressure or a temperature probe signal at X61 door

Once the pressure sensor signal type is set, the sensor range must be set as well, proceeding as follows:
1st level
2nd level
Params&Display
LoadController
Example: if a max 10bar Siemens sensor is used, the voltage output signal will be 0 V at 0 bar, while the 10 V signal will correspond to its maximum
pressure 10 bar. If the sensor is replaced with a max 16bar one, the 0 V output signal will correspond to 0 bar, while the 10 V output signal will correspond
to 16bar pressure: the parameter "MRange Press-Sens" has to be set at 16bar.
6.3

Configuration of the X62 door input signal

Following the below route access to the programming levels of the menu by means the Esc
1st level
2nd level
Params & Display
LoadController
If a boiler second probe is to be connected to terminals (1000 Ohm only), internal functions TL_ThreshOff and DiffIntervTL_SD_On are activated
automatically (see paragraph SETTING FUNCTIONS "TL_ThreshOff" AND "TL_SD_On").
3rd level
4th level
Configuration
Ext Inp X61 U/ I
3rd level
4th level
Configuration
MRange PressSens
3rd level
4th level
Configuration
Ext Inp X62 U/I
5th level
6th level
4...20 mA
2...10 V
0...10 V
0...20 mA
5th level
6th level
0...99.9 bar
0...99.9 bar
0...2000 °C
0...2000 °C
5th level
6th level
4...20 mA
2...10 V
0...10 V
0...20 mA
20
Description
Menu level for making the parameter set-
tings
Settings for the internal load controller
General configuration of the load controller
Configuration of external input X61
Set the proper value according to the probe
output.
Description
Menu level for making the parameter
settings
Settings for the internal load controller
General configuration of the load controller
End of pressure measuring range for input
X61
Set the probe value
Description
Menu level for making the parameter
settings
Settings for the internal load controller
General configuration of the load controller
Configuration of external input X62: input
signal on X62 can change setpoint or
control the load
According to the external modulator output.