Burner Specifications; Burner Model Identification; Technical Specificationstechnical Specifications; Burner Type - Unigas HTLX 1025.1 Installation Manual

Table of Contents

Advertisement

PART I: INSTALLATION MANUAL

BURNER SPECIFICATIONS

Burner model identification

Burners are identified by burner type and model. Burner model identification is described as follows.
Type
HTLX1025.1 Model
(1)

(1) BURNER TYPE

(2) FUEL
(3) OPERATION
(4) BLAST TUBE
(5) DESTINATION COUNTRY
(6) BURNER VERSION
(7) EQUIPMENT
(8) GAS CONNECTION
MICRO-PROCESSOR CON-
TROL

Technical SpecificationsTechnical specifications

Note: the Output values are referred to comburent air temperature lower than 50°C.
BURNER TYPE
Output
Fuel
Gas category
Gas rate
Gas pressure
Oil viscosity
Oil density
Oil rate
Power supply triphase
Auxiliary Power supply
Pump motor
Total power consumption
Protection
Operation
Gas train 65
Gas train 80
Gas train 100
Operating temperature
Storage Temperature
Working service*
Note1:
All gas flow rates are referred to Stm
(net calorific value H
Note2:
Maximum gas pressure= 360 mbar (with Dungs MBDLE)
Maximum gas pressure= 500 mbar (with Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure= see gas curves.
Warning:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
NOTE ON THE BURNER WORKING SERVICE: for safety reasons, one controlled shutdown must be performed every 24 hours of
continuous operation.NOTE: Choosing the nozzle for light oil, consider Hi equal to 10200 kcal/kg.
MG.
MD. S.
(2)
(3)
(4)
HTLX1025.1, HTLX1030R, HTLX1030.1
MG - Natural gas-Light oil
MD - Fully modulating
S - Standard
* - see data plate
A - Standard
Y - Special
1 = 2 valves + gas proving system 8 = 2 valves + gas proving system + maximum pressure switch
8 = 2 gas valves + gas proving system + maximum gas pressure switch
65 = DN65 - 80 = DN80 - 100 = DN100
ES = with no O
trim control, with no VSD control
2
EO = with O
trim control, with no VSD control
2
EI = with no O
trim control, with VSD control
2
EK = with O
trim control, with VSD control
2
min - max kW
3
min.-max. (Stm
/h)
cSt @ 40°C
3
kg/m
min.-max. (kg/h)
kW
kW
ØValves / Connection
ØValves / Connection
ØValves /Connection
°C
°C
3
/ h (1.013 mbar absolute pressure, 15° C temperature) and are valid for G20 gas
3
= 34,02 MJ / Stm
= 9,45 kWh / Stm
i
*.
E.
1.
65.
(5)
(6)
(7)
(8)
E- Junction box
HTLX1025.1
1565 - 8600
MG - Natural gas-Light oil
(see next paragraph)
166 - 910
132 - 725
220V/230V 3~ / 380V/400V 3N ~ 50Hz
220V/230V 2~ / 220V/230V 1N ~ 50Hz
4
4,5
Progressive - Fully modulating
2" 1/2 / DN65
3" / DN80
4" / DN100
3
);
6
EI.
(9)
HTLX1030R
HTLX1030.1
1090 - 9250
1550 - 10600
115 - 979
164 - 1122
(see Note 2)
2 - 7,4
840
92 - 780
131 - 894
4
4,5
IP54
65 / DN65
80 / DN80
3" / DN80
100 / DN100
4" / DN100
-10 ÷ +50
-20 ÷ +60
Continuous
4
4,5
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Htlx 1030rHtlx 1030.1