Figure 22 Example Of A Power Supply Connection When A Power Distribution Unit (16 Outlets) Is Used - Fujitsu ETERNUS AB Series Site Planning Manual

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

1.
ETERNUS AB/HB Installation
Outlet/Socket Specifications
For Power Distribution Unit (16 Outlets) Connections
The following diagram shows an example of a power supply connection when a power distribu-
tion unit (16 outlets) is used.
-
Current consumption of each outlet: 10A or less
-
Current consumption of each CP (four outlets: OUT1 to OUT4, or OUT5 to OUT8): 12A or less
-
Current consumption of each inlet cable: 24A or less
Figure 22 Example of a Power Supply Connection When a Power Distribution Unit (16 Outlets) Is
Used
CP
Line 0
To power supply facility
PSU: Power Supply Units
CP: Circuit Protectors
ETERNUS
Drive shelf
...
Drive shelf
Drive shelf
Controller shelf
CP
CP
Power distribution unit
CP
Distribution
board
To power supply facility
CP
Line 1
CP
Distribution
board