Download Print this page

Unitronics UniStream USC-B5-TA32 User Manual page 26

Advertisement

Analog Outputs
Number of outputs
Output range
(17)
Isolation
Resolution
Accuracy
(25°C /-20°C to 55°C)
Load impedance
Settling time
(95% of new value)
Short circuit protection
(voltage mode)
Cable
Diagnostics
(8)
26
3
Output Type
Nominal Values
0 ÷ 10VDC
0 ≤ Vout ≤ 10VDC
-10 ÷ 10VDC
-10 ≤ Vout ≤ 10VDC
0 ÷ 20mA
0 ≤ out ≤ 20mA
4 ÷ 20mA
4 ≤ out ≤ 20mA
* Overflow or Underflow is declared when an output value exceeds the
Over-range or Under-range boundaries respectively.
None
0 ÷ 10VDC – 12 bit
-10 ÷ 10VDC – 11 bit + sign
0 ÷ 20mA – 12 bit
4 ÷ 20mA – 12 bit
±0.3% / ±0.5% of full scale (Voltage)
±0.5% / ±0.7% of full scale (Current)
Voltage – 1kΩ minimum
Current – 600Ω maximum
0 ÷ 10VDC – 1.8ms (2kΩ resistive load), 3.7ms (2kΩ + 1uF load)
-10 ÷ 10VDC – 3ms (2kΩ resistive load), 5.5ms (2kΩ + 1uF load)
0 ÷ 20mA and 4 ÷ 20mA – 1.7ms (600Ω load), 1.7ms (600Ω + 10mH
load)
Yes (no indication)
Shielded twisted pair
Current – Open circuit indication
Supply level – Normal / Low or missing
User Guide
Over/Under-range Values *
10 < Vout ≤ 10.15VDC
-10.15  Vout < -10VDC
10 < Vout ≤ 10.15VDC
20 ≤ out ≤ 20.3mA
20 ≤ out ≤ 20.3mA
Unitronics

Advertisement

loading