Download Print this page

Unitronics UniStream USC-B5-TA32 User Manual page 22

Advertisement

Temperature Inputs
Number of inputs
2
Sensor Type
RTD (4, 3 and 2 wire
Thermocouple
Input range
Input type
(11)
RTD
PT100
0.00385
0.00392
0.00391
PT1000
0.00385
0.00392
RTD
NI100
0.00618
NI1000
0.00618
RTD
NI120
0.00672
RTD
NI100
0.00617
RTD
NI1000 LG
Thermocouple type
J
Thermocouple type
K
22
(10)
),
Nominal values
-200°C ≤ T ≤ 850°C
(-328°F ≤ T ≤ 1,562°F)
-100°C ≤ T ≤ 260°C
(-148°F ≤ T ≤ 500°F)
-80°C ≤ T ≤ 260°C
(-112°F ≤ T ≤ 500°F)
-60°C ≤ T ≤ 180°C
(-76°F ≤ T ≤ 356°F)
-50°C ≤ T ≤ 190°C
(-58°F ≤ T ≤ 374°F)
-200°C ≤ T ≤ 1,200°C
(-328°F ≤ T ≤ 2,192°F)
-200°C ≤ T ≤ 1,372°C
(-328°F ≤ T ≤ 2,501.6°F)
Over/Under-range Values *
Under-range:
-220°C ≤ T < -200°C
(-364°F ≤ T < -328°F)
Over-range:
850°C < T ≤ 860°C
(1,562°F < T ≤ 1,580°F)
Under-range:
-150°C ≤ T < -100°C
(-238°F ≤ T < -148°F)
Over-range:
260°C < T ≤ 270°C
(500°F < T ≤ 518°F)
Under-range:
-130°C ≤ T < -80°C
(-202°F ≤ T < -112°F)
Over-range:
260°C < T ≤ 270°C
(500°F < T ≤ 518°F)
Under-range:
-104°C ≤ T < -60°C
(-219°F ≤ T < -76°F)
Over-range:
180°C < T ≤ 210°C
(356°F < T ≤ 410°F)
Under-range:
-60°C ≤ T < -50°C
(-76°F ≤ T < -58°F)
Over-range:
190°C < T ≤ 200°C
(374°F < T ≤ 392°F)
Under-range:
-210°C ≤ T < -200°C
(-346°F ≤ T < -328°F)
Over-range:
1,200°C < T ≤ 1,250°C
(2,192°F < T ≤ 2,282°F)
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T < -328°F)
Over-range:
1,372°C < T ≤ 1,400°C
(2,501.6°F < T ≤ 2,552°F)
User Guide
Unitronics

Advertisement