Download Print this page

Unitronics UniStream USC-B5-TA32 User Manual page 23

Advertisement

Thermocouple type
T
Thermocouple type
E
Thermocouple type
R
Thermocouple type
S
Thermocouple type
B
Thermocouple type
N
Thermocouple type
C
Resistance
mV
* Overflow or Underflow
range or Under-range boundaries respectively.
Unitronics
-200°C ≤ T ≤ 400°C
(-328°F ≤ T ≤ 752°F)
-200°C ≤ T ≤ 1,000°C
(-328°F ≤ T ≤ 1,832°F)
0°C ≤ T ≤ 1,768°C
(32°F ≤ T ≤ 3,214.4°F)
0°C ≤ T ≤ 1,768°C
(32°F ≤ T ≤ 3,214.4°F)
200°C ≤ T ≤ 1,820°C
(392°F ≤ T ≤ 3,308°F)
-210°C ≤ T ≤ 1,300°C
(-346°F ≤ T ≤ 2,372°F)
10°C ≤ T ≤ 2,315°C
(50°F ≤ T ≤ 4,199°F)
0Ω ≤ R ≤ 390Ω
-70mV ≤ V ≤ 70mV
is declared when an input value exceeds the Over-
(8)
UniStream
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T <-328°F)
Over-range:
400°C < T ≤ 430°C
(752°F < T ≤ 806°F)
Under-range:
-270°C ≤ T < -200°C
(-454°F ≤ T < -328°F)
Over-range:
1,000°C < T ≤ 1,010°C
(1,832°F < T ≤ 1,850°F)
Under-range:
-50°C ≤ T < 0°C
(-58°F ≤ T < 32°F)
Over-range:
1,768°C < T ≤ 1,800°C
(3,214.4°F < T ≤ 3,272°F)
Under-range:
-50°C ≤ T < 0°C
(-58°F ≤ T < 32°F)
Over-range:
1,768°C < T ≤ 1,800°C
(3,214.4°F < T ≤ 3,272°F)
Under-range:
100°C ≤ T < 200°C
(212°F ≤ T < 392°F)
Over-range:
1,820°C < T ≤ 1,870°C
(3,308°F < T ≤ 3,398°F)
Under range:
-270°C ≤ T < -210°C
(-454°F ≤ T < -346°F)
Over-range:
1,300°C < T ≤ 1,350°C
(2,372°F < T ≤ 2,462°F)
Under-range:
0°C ≤ T < 10 °C
(32°F ≤ T < 50°F)
Over-range:
2,315°C < T ≤ 2,370°C
(4,199°F < T ≤ 4,298°F)
390Ω < R ≤ 395.85Ω
Under-range:
-71.05mV ≤ V < -70mV
Over-range:
70mV ≤ V < 71.05mV
®
PLC
23

Advertisement

loading