Installation and service manual
Version 2.5
3.7.3 LPHW reheat coil
If a reheat coil is delivered with the unit, the connecting dimensions of the reheat coil are the same as the
connecting dimensions of the Vent unit. Thus the reheat coil can be connected direct on the supply air duct.
For transport reasons the frost thermostat with connection box (1) is not fitted from the factory. It is fixed to
the water heating coil by the enclosed screws. Then fit the capillary sensor of the frost thermostat (2) by
means of the enclosed fittings, so that the sensor is placed behind the heating coil (in the air direction).
Finally fit the heating coil onto the Vent unit and plug the control cable (3) into the control panel of the Vent
unit. Please also see Section 5.
Valve motor for control of the hot water quantity may now be connected to the terminal strip under the frost
thermostat (1). Please also see the wiring diagram.