5.2 EPO Connection
EPO (Emergency power off): when the emergency occurs, such as
the failure of load, the UPS can cut off the output at once by
operating the EPO port manually.
The connection:
Normally the EPO connector is closed with a wire on the rear
panel (Fig.4-4), which is supplied in the accessory. Once the
connector is open, the UPS would stop the output and enter EPO
status (Fig.4-3).
Fig.4-3 Enable the EPO status
To recover to normal status, first EPO connector should be closed
(Fig.4-4), and press button ON more than 1 second to clear EPO
status, then UPS would stop alarm and recover to Bypass model. And
UPS needs be turned on by manual operation.
5.3 Battery installation
To install batteries in UPS, you will find the following cables in
product box:
No.
Description
1
10 AWG cable (Black)
2
10 AWG cable (Black)
3
10 AWG cable (Black)
4
10 AWG cable (Black)
5
10 AWG cable (Black)
6
10 AWG cable (Red)
Fig.4-4 Disable the EPO status
Quantity
Length
(number
(cm)
of pieces)
10
8
17
1
23
2
34
1
36
1
36
2
Remarks
F2 to F2 connector
F2 to F2 connector
F2 to F2 connector
F2 to F2 connector
F2 to F2 connector
F2 to F2 connector