Download Print this page

Njoy UPCMTOP960HASCG02B User Manual page 23

Advertisement

Available languages

Available languages

05
Converter
mode**
06
EPO/ROO***
07
EBM
Number****
DIS:
Setting UPS to normal
mode(non-CVCF mode).If
selected, the output fre-
quency will synchronize
with the input frequency
within 46~54Hz at 50Hz
or within 56~64Hz at
60Hz according to setting
program 002.(default)
Setting
UPS
ENA:
mode. If selected, the out-
put frequency will be fixed
to 50Hz or 60Hz according
to setting program 002.
But load capacity will be
derated by 40%.
EPO:
Enable EPO function, if
selected, user can Pow-
er-Off in emergency from
a remote location.(default)
ROO:
Enable ROO function, if
selected, user can power
ON/OFF from a remote
location.
You may set the number of bat-
tery package in 07 setting as
[0bP]~ [AbP]
to
CVCF
23

Advertisement

loading