Download Print this page

Njoy UPCMTOP960HASCG02B User Manual page 63

Advertisement

Available languages

Available languages

8.2. Depanare dupa codurile de eroare
Cod
Eroare
Eroare
Afisata
Output
09
Short
Over Load
14
Neg power
16
fail
Over
19
temperature
Fan fail
18
Back feed
17
05
DC short
DC Over
02
DC Under
03
DC
04
Unbalance
01
DC soft fail
Output soft
06
fail
Output Volt
08
low
Output Volt
07
high
Cauza
Posibila
Scurtcircuit la
iesire
Supraincarcare
Sarcina e pur
inductiva sau pur
capacitiva
Temperatura
ridicata
Ventilator
nefuncttional
Prezenta tensiune
inversa
Scurtcircuit cale CC
Supratensiune
cale CC
Bus Under Voltage
Bus Unbalance
Bus Soft start fail
Output Soft start
fail
Output Volt low
Output Volt high
Actiune
Deconectati toate echipamentele
de la iesire. Opriti UPS-ul. Verificati
unde s-a produs scurtcircuitul si
remediati problema inainte sa porniti
UPS-ul.
Verificati echipamentele conectate si
indepartati-le pe cele neesentiale.
Verificati sa nu existe defecte.
Deconectati echipamentele
neesentiale de la prize. Bypass -ul
va alimenta sarcinile conectate,
asigurati-va ca UPS-ul nu mai este
supraincarcat si apoi reporniti-l
Verificati ventilatorele si temperatura
ambientala.
Asigurati-va ca ventilatorul
functioneaza corect.
Luati legatura cu unitatea
de unde ati cumparat echipamentul.
Luati legatura cu unitatea
de unde ati cumparat echipamentul.
Luati legatura cu unitatea
de unde ati cumparat echipamentul.
Luati legatura cu unitatea
de unde ati cumparat echipamentul.
Luati legatura cu unitatea
de unde ati cumparat echipamentul.
63