Certification
6.1.10 Other Approvals
•
•
Declarations of conformity for each directive are available online via
Industry Online Support
6.1.10
Other Approvals
This device meets the requirements of the following additional standards:
•
•
•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
50
EU RoHS Directives (EU) 2011/65 and (EU) 2015/863
European Directive for Restriction of Hazardous Substances
China RoHS (relating to SJ/T 11364)
Management Methods for the Restriction of the Use of Hazardous Substances in
Electrical and Electronic Products
[https://support.industry.siemens.com/].
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Siemens
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
RUGGEDCOM RX5000
Equipment Manual, 11/2023, C79000-G8976-1058-15
Severity
Levels
4
4
a
Note
a
Note
4
4
4
4
3
4
Need help?
Do you have a question about the SIMATIC NET RUGGEDCOM RX5000 and is the answer not in the manual?
Questions and answers