Rohs; Other Approvals; Emc And Environmental Type Tests - Siemens SIMATIC NET RUGGEDCOM RX1510 Equipment Manual

Rugged multi service platforms
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RX1510:
Table of Contents

Advertisement

Certification
6.1.8 RoHS
6.1.8

RoHS

This device is declared by Siemens Canada Ltd. to meet the requirements of the
following RoHS (Restriction of Hazardous Substances) directives for the restricted use
of certain hazardous substances in electrical and electronic equipment:
Declarations of conformity for each directive are available online via
Industry Online Support
6.1.9

Other Approvals

This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1510 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
42
EU RoHS Directives (EU) 2011/65 and (EU) 2015/863
European Directive for Restriction of Hazardous Substances
China RoHS (relating to SJ/T 11364)
Management Methods for the Restriction of the Use of Hazardous Substances in
Electrical and Electronic Products
[https://support.industry.siemens.com/]>.
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
Siemens
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV Line-to-Ground
RUGGEDCOM RX1510
Equipment Manual, 10/2023, C79000-G8976-1055-25
Severity
Levels
4
a
Note
4
4

Advertisement

Table of Contents
loading

Table of Contents