IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
EC 60225-27
a
Siemens-specified severity levels
IEEE 1613 EMC Type Tests
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RX5000
Equipment Manual, 11/2023, C79000-G8976-1058-15
Test
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
& Interrupts
Voltage Dips
& Interrupts
Damped Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Dielectric Strength
HV Impulse
Description
ESD
6.2 EMC and Environmental Type Tests
Description
Signal ports
D.C Power ports
AC Power ports
Earth ground ports
Enclosure Ports
DC Power ports
AC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
DC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Enclosure Contact
Certification
Test Levels
10 V
10V
10V
10V
100 A/m
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
2.5 kV common, 1 kV
differential mode @1MHz
2.5 kV common, 1 kV
differential mode @1MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
10%
2 kV (Fail-Safe
Relay output)
2 kV
2 kV
5 kV (Fail-Safe
Relay output)
5 kV
5 kV
Test Levels
+/-2 kV, +/-4 kV, +/- 8 kV
Severity
Levels
3
3
3
3
 
5
 
 
 
3
3
3
4
4
3
 
 
 
 
 
 
51