Download Print this page

Error Code [6600]; Error Code [6601] - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
7-8-3

Error Code [6600]

1. Error code definition
Address overlap
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
Detail code 001: Detection of overlapped address in centralized control system
Detail code 002: Detection of overlapped address in indoor unit system
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, indoor units, LOSSNAY units, control-
lers such as ME remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
(2)
Signals are distorted by the noise on the transmission
line.
BS_07_L
Cause
Check method and remedy
Find the unit that has the same address as that of the error
source.Once the unit is found, correct the address.
Then, turn off the outdoor units, indoor units, and
LOSSNAY units, keep them all turned off for at least
five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
Refer to the following page(s). [8-4 Checking Transmission
Waveform and for Electrical Noise Interference]
43