[2-4 M-NET Address Settings ]
2-4-2

Outdoor Unit Power Jumper Connector Connection

There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the DATABOOK
for details.
System configu-
Connection to
ration
the system con-
troller
System with
one outdoor unit
System with
Not connected
multiple outdoor
units
With connection
to the indoor
unit system
With connection
to the central-
ized control
system
*1 The need for a power supply unit for transmission lines depends on the system configuration. Some controllers, such as
GB-50ADA, have a function to supply power to the transmission lines.
*2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
2-4-3

Outdoor Unit Centralized Controller Switch Setting

System configuration
Connection to the system controller Not connected
Connection to the system controller Connected *
*1 Set SW5-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
2-4-4

Room Temperature Detection Position Selection

To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor
on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON.
(Factory setting: SW1-1 set to "OFF".)
Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
When using an optional temperature sensor, install it where room temperature can be detected.
BS_02_M
Power supply unit
for transmission
lines
_
_
_
Not required
Not required
*1
Not required
(Powered from the
outdoor unit)
1
Required *
2
Group operation
Power supply switch connector connection
of units in a sys-
tem with multiple
outdoor units
_
CN41 (Factory setting)
Not grouped
Grouped
Disconnect the male connector from the fe-
male power supply switch connector (CN41)
Grouped/not
and connect it to the female power supply
grouped
switch connector (CN40) on only one of the
outdoor units.
*Connect the S (shielded) terminal on the ter-
Grouped/not
minal block (TB7) on the outdoor unit whose
grouped
CN41 was replaced with CN40 to the
ground terminal ( ) on the electric box.
Grouped/not
CN41 (Factory setting)
grouped
Centralized control switch (SW5-1) settings *
OFF (Factory setting)
ON
*2
1
chapter 2 -
5

Advertisement

loading