[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-3

Error Code [7102]

1. Error code definition
Wrong number of connected units
2. Error definition and error detection method
The number of connected indoor units is "0" or exceeds the allowable value.
3. Error source, cause, check method and remedy
After troubleshooting the error using the check methods and remedies shown below, turn the power back on.
Error source
Outdoor unit
(1)
(2)
(3)
(4)
(5)
(6)
66
- chapter 7
Cause
Number of indoor units connected to the outdoor
terminal block (TB3) for indoor/ outdoor transmis-
sion lines exceeds limitations described below.
Number of units
Restriction on the number of units
20 : 200 model
Total number of
indoor units
25 : 250 model
40 : 400 model
50 : 500 models
Total number of
LOSSNAY units
(During auto
0 or 1
address
start-up only)
Total number of
1 : HP200, 250YNW models
outdoor units
2 : HP400, 500YSNW models
Disconnected transmission line of the outdoor unit 2)
Short-circuited transmission line
When (2) and (3) apply, the following display will
appear.
ME remote controller
Nothing appears on the remote controller be-
cause it is not powered.
MA remote controller
"HO" or "PLEASE WAIT" blinks.
The model selection switch (SW5-7) on the out-
door unit is set to OFF. (Normally set to ON)
Outdoor unit address setting error
The outdoor units in the same refrigerant circuit do
not have sequential address numbers.
SW4 No. 851 is set to ON (with connection to
DIDO controller) when no DIDO controllers are
connected.
Check method and remedy
1)
Check whether the number of units
connected to the outdoor terminal
block (TB3) for indoor/ outdoor
transmission lines does not exceed
the limitation. (See (1) and (2) on
the left.)
Check (2) - (3) on the left.
3)
Check whether the transmission
line for the terminal block for cen-
tralized control (TB7) is not con-
nected to the terminal block for the
indoor/outdoor transmission line
(TB3).
4)
Check the setting for the model se-
lection switch on the outdoor unit
(Dipswitches SW5-7 on the outdoor
unit control board).
5)
Check the setting of the function
setting switch (SW4 No. 851) on
the outdoor unit.
BS_07_L