Grouped Operation Of Units In Separate Refrigerant Circuits - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-3

Grouped Operation of Units in Separate Refrigerant Circuits

(1) Sample control wiring
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF
SW5-1 OFF
OS2
53
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF
SW5-1 OFF
OS2
56
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
(2) Cautions
1) ME remote controller and MA remote controller can not
both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected
to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replacement of male power jumper connector (CN41)
must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only
one of the outdoor units.
6) A transmission booster is required in a system to which
more than 32 indoor units (26 units if one or more indoor
units of the 200 model or above is connected) are con-
nected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
16
- chapter 2
L11
Move the male connector
from CN41 to CN40.
Group
SW5-1 OFF
OS1
OC
52
51
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
M1 M2
M1 M2
S
S
To be left
unconnected
To be connected
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS1
OC
55
54
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be left
unconnected
L12
Group
IC
IC
01
03
TB5
TB15
TB5
TB15
S
1 2
M1 M2
S
1 2
A B
A B
MA
MA
L22
Group
IC
IC
02
04
TB5
TB5
TB15
TB15
M1 M2
S
1 2
S
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L11+L12 200m [656ft]
L21+L22 200m [656ft]
2) Transmission line for centralized control
L21+L31 200m [656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L12(L11)+L31+L22(L21) 1000 m [3280ft] (500 m
*1
[1640ft])
*1 If a given system includes one or more unit or remote
controller that does not support the maximum allow-
able cable distance of 1,000 m [3280 ft], the maximum
allowable cable distance in the system will be 500 m
[1640 ft]. Refer to the latest catalog for information on
which units and remote controllers support the maxi-
mum allowable cable distance of 1,000 m [3280 ft].
Interlock operation with
the ventilation unit
Group
LC
IC
06
07
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
MA
IC
05
TB5
TB15
M1 M2
1 2
S
1 2
A B
MA
m5
2
[AWG16] or larger)
BS_02_M

Advertisement

loading

This manual is also suitable for:

Puhy-hp250ynw-aPuhy-hp400ysnw-aPuhy-hp500ysnw-a