Download Print this page

Working With Refrigerant Piping; Pipe Brazing - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[1-3 Working with Refrigerant Piping ]

1-3

Working with Refrigerant Piping

1-3-1

Pipe Brazing

Perform brazing with special care to keep foreign objects (such as oxide scale, copper powder, water, and dust) out of the refrig-
erant system.
Example: Inside the brazed connection
Use of no inert gas during brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use inert gas during brazing.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
Refrigerant oil is highly hygroscopic and is likely to cause unit failure if moisture infiltrates into the system.
Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
8 -
chapter 1
Use of inert gas during brazing
BS_01_K

Advertisement

loading

This manual is also suitable for:

Puhy-hp250ynw-aPuhy-hp400ysnw-aPuhy-hp500ysnw-a