Precautions
• When the measurement unit time for the measurement target is shorter than the scan time, the measurement may not be
performed properly. Adjust the measurement unit time to twice the scan time or longer.
• If a module error occurs after normal completion, this FB does not output error completion or module error. To check for
module errors, use M+FX5-2HC_ErrorOperation (Error operation).

Parameter settings

For the parameter settings, refer to the following.
MELSEC iQ-F FX5 High-Speed Counter Module User's Manual

Performance value

Module
FX5UJ CPU module
FX5U CPU module, FX5UC CPU module
*1 When the program capacity is set to 128K steps, the processing speed may be reduced.
*2 The labels in the standard area are used.

Error code

Error code
Description
100H
The setting of i_uCH (Target channel) is out of the range. The
target channel is not within the range of 1 to 2.
101H
A module error occurred before the execution command was
turned on.
102H
The execution command was turned on while the pulse width
measurement start command of the specified channel was on.
107H
The operation mode is set to other than the pulse width
measurement mode.
10AH
The setting of i_uInputSignal (Input signal) is out of the range.
The input signal is set to other than 1 or 2.
Processing time
1.27ms
*1*2
1.06ms
Maximum scan time
0.983ms
0.809ms
Action
Execute the FB again after checking the setting.
Reset the module error, and then execute the FB again.
Turn off all pulse width measurement start commands for the
specified channel before executing the FB.
Execute the FB again after reviewing the operation mode setting.
Execute the FB again after checking the setting.
2 HIGH-SPEED COUNTER MODULE FB
2.2 M+FX5-2HC_PulseMeasure (Pulse Width Measurement)
Number of scans
2 scans
2 scans