Midea V6 Series Service Manual page 91

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50Hz
2.11 F3, F5: Temperature sensor (T6B/T6A) error
2.11.1
Digital display output
2.11.2
Description
 F3 indicates plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) error.
 F5 indicates plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) error.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.11.3
Trigger / recover condition
 Trigger condition: Temperature sensor T6A(B) is open or short-circuit.
 Recover condition: Temperature sensor T6A(B) connection ports can detect load.
 Reset method: Resume automatically.
2.11.4
Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Damaged main PCB.
90

Advertisement

Table of Contents
loading

Table of Contents