Midea V6 Series Service Manual page 79

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50Hz
2.5 E4: Temperature sensor (T3/T4) error
2.5.1
Digital display output
2.5.2
Description
 Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.5.3
Trigger / recover condition
 Trigger condition: The main control board cannot receive the feedback signal of temperature sensor T3 or T4.
 Recover condition: The main control board can receive the feedback signal of temperature sensor T3 or T4.
 Reset method: Resume automatically.
2.5.4
Possible causes
 Temperature sensor not connected properly or has malfunctioned.
 Damaged main PCB.