Midea V6 Series Service Manual page 82

Commercial air conditioners
Table of Contents

Advertisement

2.6.5
Procedure
ODU power supply is abnormal or a
phase is missing
Wires between outdoor main PCB, AC
filter boards and electric control box
power supply terminals are loose
High voltage circuit error has occurred,
such as the compressor has
malfunctioned
short-circuited
has short-circuited
Replace outdoor main PCB
Notes:
1.
The normal voltage between A and N, B and N, and C and N is 198-242V.
2.
The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
3.
The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
4.
Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
E5
1
No
No
2
, the fan motor has
3
, or the inverter module
4
No
Figure 6-2.1: Inverter module terminals
Yes
Provide normal power supply
Yes
Ensure the wires are connected properly
Yes
Replace or repair the relevant parts
V6 VRF 50Hz
81