Table 6-1.1: Error code table (continued)
Error
1
code
PL
Inverter module temperature protection
PP
Compressor discharge insufficient superheat protection
xL0
Inverter module protection
xL1
DC bus low voltage protection
xL2
DC bus high voltage protection
xL4
MCE error
xL5
Zero speed protection
xL7
Phase sequence error
Compressor frequency variation greater than 15Hz within one
xL8
second protection
Actual compressor frequency differs from target frequency by
xL9
more than 15Hz protection
Notes:
1.
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and 2
representing compressor system B. 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
2.
For some error codes, a manual restart is required before the system can resume operation.
3.
Once the EXV has been connected properly, the error code will flash to indicate that the connection has been re-established. A manual restart is then
required before the system can resume operation.
2 Troubleshooting
2.1 Warning
Warning
 All electrical work
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
standards, codes, rules, regulations and other legislation that apply in a given situation).
 Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
Content
must
be
carried
out
Remarks
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
by competent
and suitably
V6 VRF 50Hz
Manual re-start
2
required
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
qualified,
certified
and
71