3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 5-5.4 and 5-5.5 should be observed:
 The master outdoor unit can detect all the indoor units.
 The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed.
 All stop valves are open and all indoor unit EXVs are connected to their unit's PCB.
 If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more
than 100%, indoor units with total capacity equal to the total capacity of the outdoor units are currently running.
 If the outdoor ambient temperature is high, the system is being run in cooling mode with the following settings:
temperature 17°C; fan speed high.
 If the outdoor ambient temperature is low, the system is being run in heating mode with the following settings:
temperature 30°C; fan speed high.
 The system has been running normally for more than 30 minutes.
Table 6-3.4: Outdoor unit cooling mode operating parameters
Outdoor ambient temperature
Average discharge temperature
Average discharge superheat
Discharge pressure
Suction pressure
DC inverter compressor current
Table 6-3.5: Outdoor unit heating mode operating parameters
Outdoor ambient temperature
Average discharge temperature
Average discharge superheat
Discharge pressure
Suction pressure
DC inverter compressor current
134
°C
< 10
°C
60-76
°C
17-30
MPa
2.3-2.8
MPa
0.6-0.7
A
9-20
°C
< -10
-10 to 0
°C
56-74
57-76
°C
17-35
17-35
MPa
1.7-2.4
1.8-2.5
MPa
1.4-1.6
1.5-1.7
A
11-25
13-27
10 to 26
26 to 31
31 to 41
62-78
65-82
67-92
17-33
17-34
17-36
2.3-2.8
2.4-3.6
2.6-3.8
0.7-0.9
0.8-1.0
1.0-1.2
11-22
12-25
15-29
0 to 5
5 to 10
58-78
61-82
17-35
17-33
1.9-3.0
2.2-3.2
1.6-2.2
1.8-2.6
12-28
11-28
> 41
69-92
10-32
3.1-4.2
1.2-1.4
20-26
10 to 17
> 17
63-82
63-82
14-33
14-33
2.3-3.2
2.3-3.2
1.8-2.6
2.0-2.4
11-25
15-20