2.23 P5: Outdoor heat exchanger temperature protection
2.23.1
Digital display output
2.23.2
Description
 Outdoor heat exchanger temperature protection.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.23.3
Trigger / recover condition
 Trigger condition: Outdoor heat exchanger temperature (T3) ≥ 65
 Recover condition: Outdoor heat exchanger temperature (T3) < 55
 Reset method: Resume automatically.
2.23.4
Possible causes
 Outdoor unit stop valves are closed.
 Temperature sensor not connected properly or has malfunctioned.
 Indoor load too large.
 System contains air or nitrogen.
 Poor condenser heat exchange.
 High pressure side blockage.
 Main PCB damaged.
o
C.
o
C.
V6 VRF 50Hz