Midea V6 Series Service Manual page 81

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50Hz
2.6 E5: Abnormal power supply voltage
2.6.1
Digital display output
2.6.2
Description
 Abnormal power supply voltage.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.6.3
Trigger / recover condition
 Trigger condition: Outdoor unit power supply phase voltage < 165V.
 Recover condition: Outdoor unit power supply phase voltage is > 180V.
 Reset method: Resume automatically.
2.6.4
Possible causes
 Outdoor unit power supply voltage is abnormal or a phase is missing.
 Loosened wiring within electric control box.
 High voltage circuit error.
 Main PCB damaged.