V6 VRF 50Hz
2.3 E1: Phase sequence error
2.3.1
Digital display output
2.3.2
Description
Phase sequence error.
All units stop running.
Error code is only displayed on the unit with the error.
2.3.3
Trigger / recover condition
Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s.
Recover condition: Correct phase connection.
Reset method: Manually restart.
2.3.4
Possible causes
Power supply phases not connected in correct sequence.
Power supply terminals loose.
Power supply abnormal.
Main PCB damaged.