Midea V6 Series Service Manual page 85

Commercial air conditioners
Table of Contents

Advertisement

V6 VRF 50Hz
2.8 E8: Outdoor unit address error
2.8.1
Digital display output
2.8.2
Description
 Outdoor unit address error.
 All units stop running.
 Error code is only displayed on the unit with the error.
2.8.3
Trigger / recover condition
 Trigger condition: Outdoor unit address is set more than 3.
 Recover condition: Outdoor unit addresses are set from 0 to 3.
 Reset method: Manually restart.
2.8.4
Possible causes
 Invalid outdoor unit address.
 Main PCB damaged.
84