enphase IQ8MC Installation And Operation Manual page 16

Ac module
Table of Contents

Advertisement

measure 13 mm.
C. Slide the hex nut onto the cable.
D. Insert the cable into the terminator body so that each of the two wires lands on opposite
sides of the internal separator. There is a grommet inside the hex nut that should remain in
place.
E. Insert a screwdriver into the slot on the top of the terminator to hold it in place, and torque
the nut to 7 N m.
Hold the terminator body stationary with the screwdriver and turn only the hex nut to
F.
prevent conductors from twisting out of the separator.
G. Attach the terminated cable end to the PV racking with a cable clip or tie wrap so that the
cable and terminator do not touch the roof.
WARNING: The terminator cannot be reused. If you unscrew the nut, you must discard the
terminator.
16
IQ8MC, IQ8AC, and IQ8HC Installation and Operation Manual
© 2023 Enphase Energy Inc. All rights reserved.
November 2023
USM-00006-2.0

Advertisement