Lenze smd401 Operating Instructions Manual page 15

Frequency inverter 0.37 kw...22 kw
Table of Contents

Advertisement

Code
No.
Name
Configuration -
Digital input E1
Configuration -
Digital input E2
Configuration -
Digital input E3
Configuration - Relay
output
C
Network address
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Possible Settings
Lenze Selection
1
1
Activate fixed setpoint 1 (JOG1)
2
Activate fixed setpoint 2 (JOG2)
3
DC braking (DCB)
4
Direction of rotation
5
Quick stop
4
6
CW rotation
7
CCW rotation
8
UP (setpoint ramp-up)
9
DOWN (setpoint ramp-down)
10 TRIP set
3
11 TRIP reset
12 Accel/decel 2
13 Deactivate PI
14 Activate fixed PI setpoint 1
15 Activate fixed PI setpoint 2
Note
C
A
fault will occur under the following conditions:
• E1...E3 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
1
Relay is energized if
0 Ready
1 Fault
2 Motor is running
3 Motor is running - CW rotation
4 Motor is running - CCW rotation
5 Output frequency = 0 Hz
6 Frequency setpoint reached
7 Threshold (C17) exceeded
8 Current limit (motor or generator
mode) reached
9 Feedback within min/max alarm
(d46, d47) range
10 Feedback outside min/max alarm
(d46, d47) range
1
1
ENGLISH
Commissioning
• Use C37...C39 to adjust fixed setpoints
• Activate JOG3: Both terminals =
HIGH
See also C36
LOW = CW rotation
HIGH = CCW rotation
Controlled deceleration to standstill,
active LOW; Set decel rate in C13 or c03
CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected
UP = LOW and DOWN = LOW: Quick
stop; Use momentary NC contacts
Active LOW, triggers
to standstill)
NOTE: NC thermal contact from the
motor can be used to trigger this input
See also c70
See c01 and c03
Disables PI function for manual control
• Use C37...C39 to adjust fixed setpoints
• Activate fixed PI setpoint 3: Both
terminals = HIGH
247
Each controller on network must have
unique address
IMPORTANT
(motor coasts
13