Page 2
All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from Lenze AC Tech Corporation. The information and technical data in this manual are subject to change without notice. Lenze AC Tech Corporation makes no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of it’s merchantability and fitness for a given purpose.
Important • 1 smd inverter (ESMD...) After receipt of the delivery, check immediately whether the items with EPM installed delivered match the accompanying papers. Lenze does not accept any (see Section 4.2) liability for deficiencies claimed subsequently. Claim • 1 Operating Instructions •...
Safety information Safety information General Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and rotating. Some surfaces can be hot. Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation creates the risk of severe injury to personnel or damage to equipment.
Due to the many areas of liability that may be encountered when dealing with these applications, the following statement of policy applies: Lenze AC Tech Corporation inverter products are sold with no warranty of fitness for a particular purpose or warranty of suitability for use with explosion proof motors. Lenze AC Tech Corporation accepts no responsibility for any direct, incidental or consequential loss, cost or damage that may arise through the use of AC inverter products in these applications.
Technical data Technical data Standards and application conditions Conformity Low Voltage Directive (2006/95/EC) Approvals UL 508C Underwriters Laboratories - Power Conversion Equipment shielded: 50 m (low-capacitance) Max. permissible motor cable length unshielded: 100 m Input voltage phase imbalance < 2% Humidity <...
Technical data Ratings Mains Output Current Power Type [kW] Current for 60 s Voltage, frequency ESMD371L2YXA 0.37 1/N/PE 230 V OR ESMD751L2YXA 0.75 3/PE 230 V ESMD112L2YXA (180 V -0%…264 V +0%) 12.0 50/60 Hz ESMD152L2YXA 12.9 10.2 (48 Hz -0%…62 Hz +0%) ESMD222L2YXA 17.1 10.8 14.4...
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive vibration or excessive temperatures. Contact Lenze for more information. ENGLISH Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Installation Electrical installation 3.2.1 Installation according to EMC requirements Compliance with EN 61800-3/A11 Noise emission Compliance with limit value class A according to EN 55011 if installed in a control cabinet with the appropriate footprint filter and the motor cable length does not exceed 10m A Screen clamps B Control cable...
Installation Observe the following when using E.l.c.b: • Installation of E.l.c.b only between supplying mains and controller. • The E.l.c.b can be activated by: - capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables) - connecting several controllers to the mains at the same time - RFI filters Installation After a Long Period of Storage...
Installation 3.2.4 Control terminals Terminal Data for control connections (printed in bold = Lenze setting) RS-485 serial communication input RXB/TXB (B+) RS-485 serial communication input RXA/TXA (A-) Reference potential Analog input input resistance: >50 kΩ 0 … 10 V (changeable under C34) (with current signal: 250Ω)
Commissioning Commissioning Parameter setting Status/fault messages Change parameters smd404 Note If the password function is enabled, the password must be entered into C00 to access the parameters. C00 will not appear unless the password function is enabled. See C94. Electronic programming module (EPM) The EPM contains the controller’s memory.
• When C01 = LECOM (3), write speed command to C46 Load Lenze setting No action/loading complete • C02 = 1...4 only possible with Load 50 Hz Lenze settings • C02 = 2 : C11, C15 = 60 Hz Load 60 Hz Lenze settings Load OEM settings (if present)
Page 15
Commissioning Code Possible Settings IMPORTANT Name Lenze Selection Configuration - Activate fixed setpoint 1 (JOG1) • Use C37...C39 to adjust fixed setpoints Digital input E1 • Activate JOG3: Both terminals = Activate fixed setpoint 2 (JOG2) HIGH DC braking (DCB)
Page 16
Commissioning Code Possible Settings IMPORTANT Name Lenze Selection Minimum output {Hz} • Output frequency at 0% analog frequency setpoint • C10 not active for fixed setpoints or setpoint selection via c40 Maximum output 50.0 7.5 {Hz} • Output frequency at 100% analog...
Page 17
For 200 V or 400 V input High For 240 V or 480 V input Note • To simplify commissioning, the Lenze setting is preset at the factory, depending on model: C90 = 1 for 400/480 V models C90 = 2 for 230/240 V models •...
Page 18
Commissioning Code Possible Settings IMPORTANT Name Lenze Selection Holding time - • Automatic motor braking below 0.1 Hz automatic DC by means of motor DC current for the injection brake 0.0 = not active entire holding time (afterwards: U, V,...
Page 19
Commissioning Code Possible Settings IMPORTANT Name Lenze Selection Frequency setpoint {Hz} Only active if C01 is set properly via keys (C01 = 1,5,7,9,11) or Modbus Start condition Start after LOW-HIGH change at See also c70 (with mains on) terminal 28...
Page 20
Commissioning Code Possible Settings IMPORTANT Name Lenze Selection Feedback minimum alarm See C08 and c17, selections 9 and 10 Feedback maximum alarm LECOM power up Quick stop state Inhibit Serial time-out action Not active Selects controller reaction to serial timeout...
Remedy Data not valid for controller • Use EPM providing valid data Data on EPM not valid Data error • Load Lenze setting OEM data not valid EPM error EPM missing or defective Power down and replace EPM Digital inputs not E1...E3 assigned with the same...
Page 22
Troubleshooting and fault elimination Error Cause Remedy Short-circuit or overload Short-circuit Find reason for short-circuit; check motor cable Excessive capacitive charging Use shorter motor cables with lower current of the motor cable charging current Acceleration time (C12, c01) too • Increase acceleration time short •...