Omron F3SG-SR/PG Manual page 65

Safety light curtain/safety multi-light beam
Table of Contents

Advertisement

F3SG-SR/PG
Description
Safety output error
Recoverable error
Replacement-recommended error
Intelligent Tap error
Error due to change of PNP/NPN
polarity during operation
Blanking monitoring error
Configuration error
Parameter error
*1. You can check the error codes by SD Manager 3 or SD Manager 3 Mobile APP.
65
Checking by
SD Manager 3/
Indicator
SD Manager 3
Mobile APP
60, 6B, 6C
X
X
56
X
---
X
---
X
X
E7
X
X
EC
39, 3A, 3B
3C, 3E, 3F
X
X
34
F1
X
X
40
Error code
(HEX)
1
*
The OSSD lines may be short-circuited to each other or
another signal line may be short-circuited to the OSSD
line.
Wire the OSSD lines properly.
The polarity does not match between the power supply
and the OSSD lines.
Check if a correct polarity is selected for the PNP/NPN
setting according to your application. Also check:
• if the power supply (0 VDC or 24 VDC) of the Intelligent
Tap and F3SG-SR is wired as intended.
• if the OSSD lines are properly wired.
The error may occur due to a temporary cause. Identify the
cause by the status of the other LED indicator and take
measures.
---
The error may occur due to a product failure. If the
measure according to the status of the other LED indicator
does not work, it is recommended to replace the F3SG-
SR.
An error due to noise may have occurred in the internal
circuit of the Intelligent Tap.
Check the noise level in the environment.
---
The internal circuit of the Intelligent Tap may be defective.
Replace the Intelligent Tap.
An error due to noise may have occurred in the internal
circuit.
Check the noise level in the environment.
The internal circuit may be defective.
Replace the F3SG-SR.
An error is detected by the Fixed Blanking Monitoring
function or the Floating Blanking Monitoring function.
The cascading cable may be short-circuited, broken, or
disconnected. Check that the cascading cable should be
tightly connected. If the cascading cable is broken, replace
it.
The number of connected sensors or beams may have
exceeded the maximum value due to cascading.
Check the configuration.
A model name does not match between emitter and
receiver. Check that the emitter and receiver are the same
model.
An error may have occurred to the internal information of
the model name of the F3SG-SR due to effect of noise.
If other devices using the same power supply generate
noise, do not share the same power supply with other
devices, and use a separate power supply exclusively for
the safety components.
The inductive noise tends to be induced especially if the
power supply line of the machine guarded and the power
supply line of the Intelligent Tap are arranged in parallel.
Arrange the exclusive power supply near the Intelligent
Tap or lay the power supply line of the Intelligent Tap away
from the power supply line of the machine guarded.
If the power supply for the Intelligent Tap is located near
the power supply of the machine guarded and it shares the
same grounding wire, it is subject to the influence of
common mode noise.
Separate the grounding point or use it as the exclusive
ground.
An error may have occurred in the internal circuit.
Replace the F3SG-SR.
The settings do not match between the Intelligent Tap and
F3SG-SR. Perform the Backup.
The settings of the F3SG-SR may be faulty. Check if the
settings are correct.
Cause and measures