Omron F3SG-SR/PG Manual page 33

Safety light curtain/safety multi-light beam
Table of Contents

Advertisement

F3SG-SR/PG
Receiver (F3SG-SR)
Location
Indicator
Name
C
1
Scan code
or
CODE
E
2
Lockout
or
ERR
O
3
ON/OFF
or
OSSD
M
4
Maintenance
or
MAINT
P
PNP/NPN
5
or
mode
PNP
F
6
Configuration
or
CFG
S
7
Sequence
or
SEQ
Area Beam
8
---
Indicator (ABI)
Top-beam-
9
TOP
state
Bottom-beam-
10
BTM
state
*1. Refer to Troubleshooting on page 64 for more information on blinking patterns.
*2. Configurable by SD Manager 3.
*3. This is the case for the Standard Muting mode. For other muting modes, refer to User's Manual.
*4. The Area Beam Indicator closer to the "TOP" mark on the F3SG-SR blinks.
*5. The Area Beam Indicator closer to the "BTM" mark on the F3SG-SR blinks.
*6. DIP switches is on the Intelligent Tap.
Note: In the SETTING state to make settings with the SD Manager 3, the TEST, LONG and CODE indicators on the emitter and the CFG, PNP
and CODE indicators on the receiver blink. (TEST: Yellow, LONG/CODE: Green, CFG/PNP/CODE: Green)
For more information on the statuses of the LED indicators in the SETTING state, refer to User's Manual.
33
Color
Illuminated
Green
Code A is selected
Orange
Code B is selected
Automatic interference prevention by
OFF
wired synchronization being
performed
LOCKOUT state. The indicator is
illuminated in the receiver of another
sensor segment than that having a
Red
lockout error (when in cascade
connection or between the emitter and
receiver in the Wired Synchronization)
Green
Safety outputs are in ON state
Red
Safety outputs are in OFF state
LOCKOUT state due to a
recoverable error (When in cascade
Red
connection, the indicator of only the
sensor segment having the error is
illuminated)
Safety outputs are instantaneously
turned OFF due to ambient light,
Orange
vibration or noise. Or sequence error
in Muting, Pre-Reset or PSDI
Green
PNP is configured
OFF
NPN is configured
Fixed or Floating Blanking, Reduced
Resolution, Warning Zone or Slow
mode of Response Time Adjustment
Green
is enabled. Or after the Muting zone
is determined by the Dynamic Muting
function.
Yellow
INTERLOCK state
The target beams of the ABI are
Green
unblocked and the safety outputs are
turned ON
Incident light level of the target
beams of the ABI is 170% (factory
Orange
default setting (*2)) or less of ON-
threshold (for 5 to 10 s)
The target beams of the ABI are
Red
blocked
The target beams of the ABI are
unblocked (The ABI then will be
OFF
illuminated in green when the safety
outputs are turned ON.)
Blue
The top beam is unblocked
Blue
The bottom beam is unblocked
Blinking
---
LOCKOUT state. The indicator is
illuminated in the receiver of a sensor
segment having a lockout error
---
LOCKOUT state due to Safety output error,
or error due to abnormal power supply or
noise
LOCKOUT state due to a replacement-
recommended error (When in cascade
connection, the indicator of only the sensor
segment having the error blinks)
Intelligent Tap is in the LOCKOUT state
Polarity of PNP is changed to NPN, or vice
versa, during operation, and internal circuit
is defective
TEACH-IN mode, zone measurement
being performed by Dynamic Muting, or
LOCKOUT state due to Blanking
monitoring error, Configuration error or
Parameter error
Sequence or sequence error in Muting,
Pre-Reset or PSDI (*1) or Teach-in error
MUTING or OVERRIDE state. In the
MUTING state, only the ABI indicators in
the muting zone are blinking. Or the target
beams of the ABI are blocked
instantaneously
Incident light level of the target beams of
the ABI is 170% (factory default setting
(*2)) or less of ON threshold 5 to 10 s after
illuminated when incident light level of the
target beams of the ABI is 170% (factory
default setting (*2)) or less of ON threshold.
Or one muting input becomes the ON state
and the MUTING state has not been started
yet, or one muting input becomes the OFF
state and the other is not in the OFF state
yet. (*3)
LOCKOUT state due to Cap error or Other
sensor error (*4), or LOCKOUT state due to
DIP Switch setting error (*5*6)
---
MUTING/OVERRIDE state, or LOCKOUT
state due to Cap error or Other sensor error
MUTING/OVERRIDE state, or LOCKOUT
state due to DIP Switch setting error (*6)
F3SG-SRA
F3SG-SRB
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
---
---
X
---
X