4. Configuring your device
1
❶ Press any button to activate the
screen.
❷ Press mode for 5 seconds until
CF00 is displayed.
Menu CF00 Backlit display
Default setting: Back-lighting activated
Activated (automatic switch-off)
Menu CF01 Correcting the temperature measured
This menu is used to correct any difference you have noticed between the displayed temperature and the
measured temperature.
Example: If the temperature displayed by the device is 19°C and the measured temperature is 20°C, input +1°C then
confirm using OK.
Adjusts from -5°C to 5°C,
in increments of 0.1°C.
Menu CF02 Locking the buttons
This menu allows you to prohibit any changes (settings, set point, mode).
Default setting: Authorised changes
Menu CF03 Not used
Please leave the setting at 00.
Menu CF04 Adjustment of the frost protection setpoint
This menu allows you to set the Frost protection set point temperature (from 5°C to 16°C). Default setting: 7°C
Adjusts from +5°C to +16°C,
in increments of 0,5°C.
> 5s
2
❸ Press + or - to adjust the setting,
and on mode to move to the next
menu.
Deactivated
No locking
Locking active
mode
3
The "--" display in a CFxx menu indicates that
several receivers associated with the Tybox
mode
have different values.
In order to change this setting, the unit
must have been running for at least 2 hours
beforehand.
Default setting: 0°C
If locked, the screen will display "----".
To temporarily unlock, simultaneously press
and hold the + and - buttons for 5 seconds.
mode
> 5s
4
❹ Press mode for 5 seconds to exit
the configuration menu or, after a
period of 2 minutes without activity,
the Tybox validates the change of
parameter and returns to standby.
5