Veichi SI23 Manual page 33

Solar pump
Hide thumbs Also See for SI23:
Table of Contents

Advertisement

Bus
F10.18(0x0A12)
undervoltage
suppression gain
Bus
F10.19(0x0A13)
undervoltage
protection point
Input and output
phase loss
F10.20(0x0A14)
protection
options
Ground short
F10.22(0x0A16)
circuit protection
option
Fan ON/OFF
F10.23(0x0A17)
control selection
V/F SVC
Set the response effect of undervoltage
suppression.
V/F SVC
The lower limit voltage allowed by the set bus
voltage. Below this value, the VFD reports an
undervoltage fault.
V/F SVC FVC
Set whether the input and output phase loss
protection functions are enabled.
LED "0" digit: Output phase loss protection.
0: Off
1: On
LED "00" digit: Input phase loss protection.
0: Off
1: On, detected the input missing phase report
warning A.ILF, continue to run
2: Turn on, detect input missing phase report
fault E.ILF, free stop
V/F SVC FVC
Set whether the VFD output and the VFD
cooling fan ground short circuit protection
function are enabled.
LED "0" digit: Output short circuit protection.
0: Off 1: On
LED "00" digit: Fan to ground short circuit
protection.
0: Off
1: On
Set the VFD cooling fan operation mode.
0: The fan runs after the VFD is powered on.
1: After the shutdown, the fan operation is
related to temperature, and the operation is
running.
2: After the shutdown, the fan stops after
F10.24, and the operation is related to
temperature.
32
SI23 Solar Pump VFD Manual
100.0%
(0.0%~500.0%)
T3
T3: 320
overvoltage
S2: 190
point: 820V
(T3: 300~400
(750~840)
S2: 160~240)
S2
Also subject to
overvoltage
overvoltage limit
point 400V
(360~410)
021
(000~121)
11
(00~12)
1
(0~2)