Power failure
F07.06(0x0706)
restart action
selection
F07.10(0x070A)
Stop mode
● Protection Parameters
Parameter
Function
(address)
Description
Overcurrent
F10.00(0x0A00)
suppression
Overcurrent
F10.01(0x0A01)
suppression
point
Bus overvoltage
F10.12(0x0A0C)
suppression
point
Bus
F10.16(0x0A10)
undervoltage
suppression
Bus
undervoltage
F10.17(0x0A11)
suppression
point
V/F SVC FVC
0: Invalid
1: Valid
V/F SVC FVC
0: Deceleration stop
1: Free stop
Range of settings and definition
V/F SVC FVC
The automatic limiting output current does not
exceed the set overcurrent suppression point to
prevent overcurrent faults from being triggered
by excessive current.
0: Inhibition is always valid
1: Acceleration/deceleration is valid, constant
speed is invalid
V/F SVC FVC
Set the load current limit level, 100%
corresponds to the rated motor current.
V/F SVC FVC
Set bus voltage value for trigger overvoltage
suppression function.
V/F SVC FVC
When the bus voltage is lower than the
undervoltage suppression point, the operating
frequency is automatically adjusted to suppress
the bus voltage from decreasing, preventing the
undervoltage fault.
0: Off
1: On
V/F SVC FVC
Set bus voltage value for trigger undervoltage
suppression function.
31
SI23 Solar Pump VFD Manual
0
(0~1)
0
(0~1)
Factory default
Notes
(setting range)
0
(0~1)
160.0%
(0.0%~300.0%)
T3
T3: 780
overvoltage
S2: 370
point: 820V
(T3: 650~760
(750~840)
S2: 340~380)
S2
Also subject to
overvoltage
overvoltage limit
point: 400V
(360~410)
0
(0~1)
T3
T3: 430
overvoltage
S2: 240
point: 820V
(T3: 350~450
(750~840)
S2: 180~260)
S2
Also subject to
overvoltage
overvoltage limit
point 400V
(360~410)