Veichi SI23 Manual page 28

Solar pump
Hide thumbs Also See for SI23:
Table of Contents

Advertisement

● Motor Parameters
Parameter
Function
(address)
Description
F02.00(0x0200)
Motor type
F02.01(0x0201)
Pole number
Motor rated
F02.02(0x0202)
power
Motor rated
F02.03(0x0203)
frequency
Motor rated
F02.04(0x0204)
speed
Motor rated
F02.05(0x0205)
voltage
Motor rated
F02.06(0x0206)
current
Motor parameter
F02.07(0x0207)
auto-tuning
selection
Motor online
F02.50(0x0232)
learning function
selection
Range of settings and definition
V/F SVC FVC
Set the type of motor
0: Asynchronous motor (AM)
1: Reserved
V/F SVC FVC
Set the number of motor stages.
V/F SVC FVC
Set the rated power of the motor.
V/F SVC FVC
Set the rated frequency of the motor.
V/F SVC FVC
Set the rated speed of the motor.
V/F SVC FVC
Set the rated voltage of the motor.
V/F SVC FVC
Set the rated current of the motor.
V/F SVC FVC
After the parameter auto-tuning is completed,
the set value of [F02.07] will be automatically
set to "0".
0: No operation
1: Rotary self-tuning
2: Static self-tuning
3: Stator resistance self-tuning
V/F SVC FVC
0: Invalid
1: Power-on self-learning
2: Run the initial segment self-learning
3: Self-learning in operation
27
SI23 Solar Pump VFD Manual
Factory default
Notes
(setting range)
0
(0~1)
4
(2~98)
Model setting
(0.1kW~
1000.0kW)
Model setting
(0.01Hz~
Maximum
frequency)
Model setting
(0rpm~
65000rpm)
Model setting
(0V~1500V)
Model setting
(0.1A~3000.0A)
0
(0~3)
0
(0~3)

Advertisement

Table of Contents
loading

Table of Contents