Mitsubishi Heavy Industries FDT200VSAWPVH Service Manual page 99

Micro inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Indoor control PCB
Remote control:
E35
Outdoor control PCB
Outdoor inverter
1. Applicable model
All models
2. Error detection method
For the error detection method,
refer to cooling high pressure
protective control in the
protective control by controlling
compressor rotation speed of
microcomputer control function
for corresponding models.
3. Condition of error displayed
When outdoor heat exchanger
temperature anomaly is detected
5 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop
4. Presumable cause
• Defective outdoor heat
exchanger temperature sensor
• Defective outdoor unit control
PCB
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
• Excessive refrigerant amount
Note:
LED
Green
Keeps flashing
Keeps flashing
Yellow LED
PCB
Keeps flashing
5. Troubleshooting
outdoor heat exchanger
unit operating in the
(measured actually) at
detection of error
* For the contents of control, refer to cooling high pressure protective control
in the protective control by controlling compressor rotation speed of
microcomputer control function for corresponding models.
Red
Content
Stays OFF
Cooling overload operation
1-time flash
Diagnosis
* For the characteristics of outdoor
heat exchanger temperature
Are the
sensor, refer to E37.
characteristics of
NO
temperature sensor
normal?
YES
Is the
YES
state of cooling
overload?
NO
Is the high
pressure control
NO
normal?
YES
Is
the temperature
NO
correct?
YES
98
-
-
'21 • PAC-SM-383
Countermeasure
Replace outdoor heat
exchanger temperature
sensor.
Check unit side.
• Isn't the air circulation
of outdoor unit short-
circuited?
• Are installation spaces
adequate?
• Isn't there any fouling
or clogging on heat
exchanger?
Control operation check *
Defective outdoor unit
control PCB➞Replace.
Excessive refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.