Mitsubishi Heavy Industries FDT200VSAWPVH Service Manual page 92

Micro inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E16
Remote control:
Note (1) Value in (   ) is for FMi2.
1. Applicable model
FDU series
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of Error displayed
When actual rotation speed of
indoor fan motor drops to lower
-1
than 200min
for 30 seconds
continuously, the compressor
and the indoor fan motor
stop. After 2 seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective indoor unit power
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on indoor unit control
PCB
• Blown fuse
• External noise, surge
• Indoor unit control PCB
anomaly
• Motor control PCB
Note:
LED
Green
Red
Keeps flashing 1 ( 2 ) -time flash
Indoor
Keeps flashing Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Po From previous page
•In case of FMi2
(1)
Is DC280V
detected between
of fan power PCB connector
CNM2?
YES
Power source reset
Is it normalized?
91
-
Content
Indoor fan motor anomaly (2/2)
(FDU series)
Note(1)
for GND
NO
NO
Is the fuse F2 blown?
YES
NO
YES
-
'21 • PAC-SM-383
Countermeasure
Check power source
voltage.
Replace faulty fan motor
and indoor unit power
PCB.
Replace fan motor.
〔 If the error persists after
replacing the fan motor,
replace the indoor unit
control PCB 〕
Malfunction by temporary
noise.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents