(11) Drain pump control
(a) This control is operated when the inverter frequency is other than 0 Hz during the cooling operation and automatic
cooling and dehumidifying operations.
(b) Drain pump ON condition continues for 5 minutes even when it enters the OFF range according to (a) above after
turning the drain pump ON, and then stops. The 5-minute delay continues also in the event of anomalous stop.
(c) The drain pump is operated with the 5-minute delay operation when the compressor is changed from ON to OFF.
(d) Even in conditions other than the above (such as heating, fan, stop, cooling thermostat OFF), the drain pump control is
performed by the drain detection.
(e) Following settings can be made using the indoor function setting of the wired remote control.
(i)
Standard in cooling
Operate in standard & heating : Drain pump is run during cooling and heating.
(ii)
(iii)
(iv)
Operate in standard & fan : Drain pump is run during cooling and fan.
Note (1) Values in 〔
(12) Drain pump motor (DM) control
(a) Drain detection switch is turned ON or OFF with the float switch (FS) and the timer.
[ * 1] Drain detection switch is turned "ON" when the float switch "Open" is detected for 3 seconds continuously in
the drain detectable space.
[ * 2] Drain detection switch is turned "OFF" when the float switch "Close" is detected for 10 seconds continuously.
(i) It detects always from 30 seconds after turning the power ON.
1) There is no detection of anomalous draining for 10 seconds after turning the drain pump OFF.
2) Turning the drain detection switch "ON" causes to turn ON the drain pump forcibly.
3) Turning the drain detection switch "OFF" releases the forced drain pump ON condition.
(b) Indoor unit performs the control A or B depending on each operating condition.
Stop
Compressor ON
Compressor OFF
(i) Control A
1) If the float switch detects any anomalous draining condition, the unit stops with the anomalous stop (displays E9)
and the drain pump starts. After detecting the anomalous condition, the drain pump motor continues to be ON.
2) It keeps operating while the float switch is detecting the anomalous condition.
(ii) Control B
If the float switch detects any anomalous drain condition, the drain pump motor is turned ON for 5 minutes, and at 10
seconds after the drain pump motor OFF it checks the float switch. If it is normal, the unit is stopped under the normal
mode or, if there is any anomalous condition, E9 is displayed and the drain pump motor is turned ON. (The ON
condition is maintained during the drain detection.)
(13) Operation check/drain pump test run operation mode
(a) If the power is turned on by the DIP switch (SW7-1) on the indoor unit control PCB when electric power source is
supplied, it enters the mode of operation check/drain pump test run. It is ineffective (prohibited) to change the switch
after turning power on.
(b) When the communication with the remote control has been established within 60 seconds after turning power on by the
DIP switch (SW7-1) ON, it enters the operation check mode. Unless the remote control communication is established,
it enters the drain pump test run mode.
Note (1) To select the drain pump test run mode, disconnect the remote control connector (CnB) on the indoor unit PCB to shut down the remote control
communication.
: Drain pump is run during cooling.
Operate in heating & fan : Drain pump is run during cooling, heating and fan.
〕 are for the RC-EX3A model.
Normal state
[*1]
Indoor unit operation mode
Cooling
Dry
(1)
Control A
Control B
-
Drain detection switch ON
Fan
Heating
(2)
Notes (1) Including the stop from the cooling, dehumidifying, fan
17
-
'21 • PAC-SM-383
Normal state
[*2]
and heating, and the anomalous stop
  (2) Including the "Fan" operation according to the
mismatch of operation modes