(2) Compressor start control
(a)
Compressor starts upon receipt of the thermostat ON signal from the indoor unit.
(b) However, at initial start of heating mode after turning on the power source breaker, it may enter the standby state for
maximum 30 minutes ("
compressor.
If the heating operation is selected from the remote control when the outdoor unit is in the standby state,
"
PREPARATION" is displayed for 3 seconds on the remote control.
(3) Compressor soft start control
(a) Compressor protection start I
[Control condition]
Normally, the compressor operation frequency is raised in this start pattern.
[Control contents]
(i) Starts with the compressor's target frequency at A rps.
However, when the outdoor air temperature (Tho-A) is 35°C or higher during cooling/dehumidifying or the indoor
return air temperature (Thi-A) is 25°C or higher during heating, it starts at C rps.
(ii) At 30 seconds after the start of compressor, its target frequency changes to B rps and the compressor is operated for
2 - 4 minutes with its operation frequency fixed at B rps.
Model
FDC200-280
(b) Compressor protection start III
[Control condition]
Number of compressor starts is only 1 counted after the power source breaker ON.
[Control contents]
Operates by selecting one of following start patterns according to the operation mode and the outdoor air temperature
(Tho-A).
(i) Low frequency operation control during cooling/dehumidifying.
[Control condition]
Upon establishing the conditions of compressor protection start III, the low frequency operation control is
performed during cooling/dehumidifying.
[Control contents]
1) Starts with the compressor's target frequency at A rps. When the outdoor air temperature (Tho-A) is 35°C or
higher, it starts at C rps.
2) At 30 seconds after the compressor start, the compressor's target frequency is changed to B rps and the
compressor's operation frequency is fixed for 10 minutes.
Model
FDC200-280
(ii) Low frequency operation control during heating.
[Control condition]
When the conditions of compressor protection start III are established and one of following conditions a), b) is satisfied,
the low frequncy operation control is performed during heating.
a) At 30 minutes or more after turning the power source breaker on
b) When compressor under dome sensor temperature (Tho-C) is 4°C or higher and the difference between
compressor under dome sensor temperature and outdoor air sensor temperature (Tho-C-Tho-A) is 4°C or higher.
[Control contents]
a) Starts the compressor with its target frequency at A rps. However, when the indoor return air temperature (Thi-A)
is 25°C or higher, it starts at C rps.
b) At 30 seconds after the start of compressor, the compressor's target frequency is changed to B rps and the
compressor's operation frequency is fixed for 10 minutes.
Model
FDC200-280
PREPARATION" is displayed on the remote control) in order to prevent the oil loss in the
Operation mode
Cooling/Dehumidifying
Heating
Operation mode
Cooling/Dehumidifying
Operation mode
Heating
A rps
B rps
55
55
55
55
A
B
rps
rps
55
30
A
B
rps
rps
55
30
30
-
-
'21 • PAC-SM-383
C rps
30
30
C
rps
30
C
rps
30