(8) Thermostat operation
(a) Cooling
(i) Thermostat is operated with the room temperature control.
(ii) Thermostat is turned ON or OFF relative to the setting room temperature as shown below.
Thermostat OFF
(iii) Thermostat is turned ON when the room temperature is in the range of -1 < Setting room temperature < +1 at the start
of cooling operation (including from heating to cooling).
(b) Heating
(i) Thermostat is operated with the room temperature control.
(ii) Thermostat is turned ON or OFF relative to the setting room temperature as shown below.
Heater ON
(iii) Thermostat is turned ON when the room temperature is in the range of -1 < Setting room temperature < +1 at the start
of heating operation (including from cooling to heating).
(c) Fan control during heating thermostat OFF
(i) Following fan controls during the heating thermostat OFF can be selected with the indoor function setting of the wired
remote control.
① Low fanspeed (Factory default) ② Set fan speed ③ Intermittence ④ Fan OFF
(ii) When the "Low fan speed (Factory default)" is selected, the following speed is used for the indoor fans.
・ ForDCmotor:ULo
(iii) When the "Set fan speed" is selected, it is operated with the set fan speed also in the thermostat OFF condition.
(iv) If the "Intermittence" is selected, following controls are performed:
1) If the thermostat is turned OFF during the heating operation, the indoor unit moves to the hot control and turns OFF
the indoor fan if the heat exchanger temperature sensors (both Thi-R1 and R2) detect 25°C or lower.
2) Indoor fan OFF is fixed for 5 minutes. After the 5 minutes, the indoor fan is operated at ULo for 2 minutes. In the
meantime the louver is controlled at level.
3) After operating at ULo for 2 minutes, the indoor fan moves to the state of 1) above.
4) If the thermostat is turned ON, it moves to the hot start control.
5) When the heating thermostat is turned OFF, the remote control displays the temperature detected at the fan stop and
revises the temperature later when the indoor fan changes from ULo to stop.
The remote control uses the operation data display function to display temperatures and updates values of
temperature even when the indoor fan is turned OFF.
6) When the defrost operation starts while the heating thermostat is turned OFF or the thermostat is turned OFF during
defrost operation, the indoor fan is turned OFF. (Hot keep or hot start control takes priority.) However, the suction
temperature is updated at every 7-minute.
7) When the heating thermostat is turned ON or the operation is changed to another mode (including stop), this control
is stopped immediately, and the operating condition is restored.
(v) When the "Fan OFF" is selected, the fan on the indoor unit of which the thermostat has been turned OFF, is turned OFF.
The same occurs also when the remote control sensor is effective.
+1
-1
Setting room temperature
Thermostat ON
-1
-1
+1
3 C ◦
Setting room temperature
-
Thermostat ON
Thermostat OFF
+1
Heater OFF
15
-
'21 • PAC-SM-383
Temperature drop
Temperature rise
Temperature drop
Temperature rise