Mitsubishi Heavy Industries FDT200VSAWPVH Service Manual page 79

Micro inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Remote control:
WAIT
1. Applicable model
All models
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Faulty noise filter
• Faulty indoor unit control
PCB
• Faulty outdoor unit control
PCB
• Faulty inverter PCB
• Faulty fan motor
Note:
LED
Green
Red
Keeps flashing
Stays OFF
Indoor
Keeps flashing
2-time flash
Outdoor
5. Troubleshooting
Diagnosis
Diagnosis for when the outdoor unit
control PCB LED is turned off
From previous
Shut down the breaker and back on
page
again the breaker 3 minutes later.
NO
Does it reset normally?
Is AC380/415V
detected at the noise filter
secondary side?
YES
Is DC280/373V detected at CNA2?
YES
Is fuse
〔250V, 2A〕 on the outdoor unit control
PCB blown?
NO
Is DC5V
detected on the outdoor unit control PCB (Between
- of CNV)?
YES
Is DC5V detected
if the connector of outdoor fan motor
is disconnected?
YES
Is DC5V detected
if the inverter power source connector (CNI2)
is disconnected?
78
-
Content
Communication error at
initial operation (2/2)
YES
NO
NO
YES
NO
NO
NO
YES
-
'21 • PAC-SM-383
Countermeasure
Normal. (Malfunction by
noise)
Replace noise filter.
Check connection of diode
stack and electrolytic
capacitor by refering main
electrical circuit diagram.
Defective outdoor unit
control PCB ➞ Replace.
Defective outdoor unit
control PCB ➞ Replace.
Defective outdoor fan
motor
Defective inverter PCB
➞ Replace.
Defective outdoor unit
control PCB ➞ Replace.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents