Mitsubishi Heavy Industries FDT200VSAWPVH Service Manual page 74

Micro inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Remote control:
None
1. Applicable model
Except FDT, FDTC series
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor unit control
PCB
• Broken harness
• Faulty outdoor unit control
PCB (Noise filter)
Note:
LED
Green
Red
Indoor Stays OFF Stays OFF
(Power source to indoor unit control PCB)
Outdoor
2-time flash
Keeps flashing
5. Troubleshooting
Diagnosis
Is
AC220/240V
detected between
and
on the terminal block
of indoor
unit?
YES
Note(1) FDUM, FDE:F1, F2
(1)
Are fuses OK?
YES
(1)
Is DC5V
detected between -
of CNW2?
(FDU:CNW1)
Note (1)
YES
Is JX1 open?
73
-
Content
Power source system error
NO
Is
AC380/415V
for 3-phase unit detected
between ,
and
on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
and
on the terminal
block of outdoor
unit?
FDU:F3
NO
Is the
check of resistance between
- of CNW0
(FDU:T1-T2)
OK?
YES
Is the
checked result
of resistance of FM,
LM, etc
OK?
for GND
-
'21 • PAC-SM-383
Countermeasure
Defective outdoor unit
NO
control PCB (Noise filter).
➞ Replace.
Misconnection or breakage
YES
of connecting wires.
Defective indoor unit
NO
control PCB ➞ Replace.
Replace FM, LM, etc.
NO
Replace fuse.
YES
NO
Defective indoor unit
control PCB ➞ Replace.
Open JX1.
NO
Defective indoor unit
YES
control PCB ➞ Replace.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents