2 Delivery and handling

Transport

F470 should be transported and stored vertically in a dry
place. The F470 may, however, be carefully laid on its
back when being moved into a building.

Assembly

• Place F470 on a solid foundation indoors that can take
the heat pump's weight. Use the product's adjustable
feet to obtain a horizontal and stable set-up.
Because water comes from F470, the floor coating is
important. A waterproof floor or floor membrane is
recommended.
20-55 mm
30 - 50 mm
• Install with its back to an outside wall, ideally in a room
where noise does not matter, in order to eliminate
noise problems. If this is not possible, avoid placing
it against a wall behind a bedroom or other room
where noise may be a problem.
• Wherever the unit is located, walls to sound sensitive
rooms should be fitted with sound insulation.
• Route pipes so they are not fixed to an internal wall
that backs on to a bedroom or living room.
• The heat pump's installation area should always have
a temperature of at least 10 °C and max 30 °C.
12
Chapter 2 | Delivery and handling
0
R
INSTALLATION AREA
Leave a free space of 800 mm in front of the product.
Leave free space between F470 and wall/other ma-
chinery/fittings/cables/pipes etc. It is recommended that
a space of at least 10 mm is left to reduce the risk of
noise and of any vibrations being propagated.
80
NOTE
Ensure that there is sufficient space (300 mm)
above F470 for connecting ventilation ducts.
800
NIBE F470