Page 1
IHB EN 2036-1 INSTALLER MANUAL 631010 Exhaust air heat pump NIBE F470 1x230V...
Page 2
Quick guide Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button functions can be found on page How to scroll through menus and make different settings is described on page Set the indoor climate INDOOR CLIMATE HOT WATER HEAT PUMP...
Installation alternative General ventilation connection 12 Technical data Ventilation flow Dimensions and setting-out coordinates Adjusting ventilation Technical specifications Dimension and ventilation connections Energy labelling Electrical circuit diagram 5 Electrical connections General Item register Connections Settings NIBE F470 Table of Contents...
Read the User Manual. prevent water pockets, and it must also be frost-proof. Read the Installer Manual. F470 must be installed via an isolator switch. The cable area has to be dimensioned based on the fuse rating used. Chapter 1 | Important information...
The area must be ventilated whilst the work is being carried out. There NIBE F470 Chapter 1 | Important information...
Page 6
This must be reported to the equipment owner, so that all parties have been informed. Chapter 1 | Important information NIBE F470...
Page 7
• Containers must be stored upright. • Ensure that the cooling system is grounded before the system is filled with refrigerant. NIBE F470 Chapter 1 | Important information...
Page 8
The equipment must be of the system. suitable for the collection of combustible re- frigerant. Check that the refrigerant container is on the scales before starting to collect. Chapter 1 | Important information NIBE F470...
Maintenance and repair that requires the skill of another person must be carried out under the supervision of someone with the above expertise. NIBE F470 Chapter 1 | Important information...
Building Regulations, England & Warranty and insurance information Wales Approved Document F1 and Scotland Technical Thank you for installing a new NIBE heat pump in your Standard Section 3.14 Ventilation. Only this will ensure home. hygienic room air and prevent any dampness to the building structure.
Setting trim valve, number of turns from closed position Expansion vessel T&P valve Tundish Electricity (page Connections Main voltage Phase voltage Fuses heat pump Fuses property Outside sensor Room sensor Safety breaker Earth circuit-breaker Miscellaneous Benchmark checklist NIBE F470 Chapter 1 | Important information...
Assembly 5 - 40 mm • Place F470 on a solid foundation indoors that can take the heat pump's weight. Use the product's adjustable feet to obtain a horizontal and stable set-up. Because water comes from F470, the floor coating is important.
Remove the upper panel by pulling it straight out. Remove the screws from the lower edge of the front panel. Lift the panel out at the bottom edge and up. Pull the panel towards yourself. NIBE F470 Chapter 2 | Delivery and handling...
Page 15
Overflow pipe, safety valve hot water heater Choke Overflow pipe, safety valve climate system EMC-filter Overflow pipe, condensation Switch W130 Network cable for NIBE Uplink MISCELLANEOUS Rating plate Serial number plate UB1-2 Cable gland Not visible in the image Designations according to standard EN 81346-2.
Supply air fan HQ10 Exhaust air filter HQ11 Supply air filter AA102 Filter cover, exhaust air Filter cover, supply air GQ10 Not visible in the image Placed on the back of the product Chapter 3 | The heat pump design NIBE F470...
15 mm 35 mm up to 27 m 1.4 mm <G3>/4 22 mm 28 mm up to 9 m 1.0 mm <G3>/4 22 mm 35 mm up to 18 m 1.4 mm NIBE F470 Chapter 4 | Pipe and ventilation connections...
Page 18
The volume of the pressure expan- There should not normally be any problem installing sion vessel (CM1) is 10 litres and F470 in hard water areas, as the operating temperature it is pre-pressurised as standard to is 50-60°C. 0.5 bar (5 mvp). As a result, the CLEANING THE CLIMATE SYSTEM maximum permitted height “H”...
SYSTEM DIAGRAM Dimensions and pipe F470 consists of a heat pump, water heater, immersion heater, fans, circulation pump and control system.F470 connections is connected to the ventilation system and heating me- dium circuit. When the exhaust air at room temperature passes through the evaporator, the refrigerant evaporates be- cause of its low boiling point.
A climate system is a system that regulates indoor valve (RN1). The supply air temperature must be approx- comfort with the help of the control system in F470 and imately the same as the indoor temperature, preferably for example radiators, underfloor heating/cooling, fan a few degrees lower.
If it is possible to use a water heater with an immersion heater, connect it as illustrated below. CONNECTING HOT WATER CIRCULATION A circulation pump can be controlled by F470 to circulate the hot water. The circulating water must have a tem- perature that prevents bacterial growth and scalding, and national standards must be satisfied.
Exhaust air duct (kitchen fan) must not be connected to connection F470. To prevent cooking odours from being led to the F470, the distance between the kitchen fan and the exhaust • Ventilation installation must be carried out in accord- air valve must be observed.
• F470 must be equipped with a separate earth-fault person may replace it to prevent any danger breaker (30 mA). and damage. • F470 must be installed via an isolator switch. The cable area has to be dimensioned based on the fuse rating NOTE used.
Page 25
The temperature limiter is reset by firmly pressing in its button (FQ11-SF2) using a small screw- driver. Insert the screwdriver (A) and pry the catch carefully downwards (B). Angle out the cover and remove it. NIBE F470 Chapter 5 | Electrical connections...
20 cm from high voltage cables. POWER CONNECTION F470 must be installed via an isolator switch with a minimum breaking gap of 3mm. Minimum cable area must be sized according to the fuse rating used. Sup- plied cable (length approx.
Page 27
AA3-X6 AA3-X6 ROOM SENSOR F470 is supplied with a room sensor enclosed (BT50). The room sensor has a number of functions: Shows current room temperature in the display on F470. Option of changing the room temperature in °C.
Power in emergency mode The immersion heater’s output in emergency mode is set with the dipswitch (S2) on the immersion heater circuit board (AA1) according to the table below. Factory setting Chapter 5 | Electrical connections NIBE F470...
LOAD MONITOR activate temp lux Integrated load monitor not used F470 is equipped with a simple form of integrated load not used monitor, which limits the power steps for the electric not used additional heat by calculating whether future power...
Page 30
C NO NC External activation of functions AA3-X7 AA3-X7 An external switch function can be connected to F470 to activate various functions. The function is activated The picture shows the relay in the alarm position. during the time the switch is closed.
Page 31
NIBE ECS 40/41 should be used for optimum operation. External blocking of functions An external switch function can be connected to F470 for blocking various functions. The switch must be po- tential-free and a closed switch results in blocking.
Externt AA3-X7 Circulation pump Connecting accessories Instructions for connecting accessories are provided in the manual accompanying the accessory. See page 61 for the list of the accessories that can be used with F470. Chapter 5 | Electrical connections NIBE F470...
Close the filling valve (QM11) and (QM13). Reduce the boiler pressure to the normal working range (approx. 1 bar) by opening the vent valves (QM20) and (QM21) or the safety valve (FL2). NIBE F470 Chapter 6 | Commissioning and adjusting...
There must be water in the climate system before the switch is set to " ". Set switch (SF1) on F470 to position "". If the start guide is left on this page it closes Follow the instructions in the display’s start guide.
Page 35
Airflow Luftflöde (l/s) (l/s) Specific fan power Available pressure Tryck (Pa) 1,2 1,4 0,8 1,0 Airflow Luftflöde (l/s) The diagram shows the SFP rating with both the fans’ power consumption ( (l/s) NIBE F470 Chapter 6 | Commissioning and adjusting...
Page 36
Vent the coil using the venting screw (QM21) NOTE repeatedly in order to ensure the circulation Select operating mode "auto" or "manual" when through the coil. the heat pump is to run on recovery again. Chapter 6 | Commissioning and adjusting NIBE F470...
Page 37
• constant pressure auto adapt (CPAA) • proportional pressure (PP) • constant pressure (CP) • constant curve (CC). The circulation pump’s factory setting is CP, speed 3. Flow Flöde (l/s) Setting PPAA LED indication NIBE F470 Chapter 6 | Commissioning and adjusting...
The rotor is blocked. Wait or release the rotor shaft. ature, and thereby energy-efficient operation. Based on this curve, the F470 determines the temperature of the water to the climate system (the supply temperature) and thus the indoor temperature.
Page 41
You can now select to take read outs for different outdoor temperatures by turning the control knob to the right or left and read off the corresponding flow temperature. Press the OK or Back button to exit read off mode. NIBE F470 Chapter 6 | Commissioning and adjusting...
Page 42
2 Under floor heating can be dimensioned very differently. The above example refers to a system where the supply temperature needs to be approximately 35 – 40 °C or 45 – 50 °C on the coldest day. Chapter 6 | Commissioning and adjusting NIBE F470...
• confirm selections of sub menus/options/set values/page in the start guide. BACK BUTTON The back button is used to: • go back to the previous menu. • change a setting that has not been confirmed. NIBE F470 Chapter 7 | Control - Introduction...
These two symbols indicate whether the INDOOR CLIMATE HOT WATER Hot water temp. compressor or addition is blocked in F470. These can, for example, be blocked depend- ing on which operating mode is selected in menu 4.2, if blocking is scheduled in menu 4.9.5 or if an alarm has occurred that blocks...
Page 45
Back button. Mark the applicable option. One of the options is pre-selected (white). Press the OK button to confirm the selected option. The selected option has a green tick. NIBE F470 Chapter 7 | Control - Introduction...
Page 46
(at the page number) has been marked. Press the OK button to skip between the steps in the start guide. If the start guide is left on this page it closes automatically in 60 min Chapter 7 | Control - Introduction NIBE F470...
Quick starting the compressor. stop temp. per. increase NOTE Setting range: 55 – 70 °C Incorrect settings in the service menus can Factory setting: 60 °C damage the heat pump. NIBE F470 Chapter 8 | Control - Menus...
Page 50
Check the max floor temperature with your Here you set the max. electrical output of the internal floor supplier. electric additional heat in F470 during normal operation and overcapacity mode (SG Ready), as well as the fuse MENU 5.1.4 - ALARM ACTIONS size and transformer ratio for the installation.
Page 51
Here you can set transfer time between heating and hot See the accessory installation instructions for function water production in F470. During the transfer time the description. compressor maintains the stop temperature that applied during hot water production.
Page 52
4.2. It is possible to save a floor drying log that shows when the concrete slab has reached the correct temperature. See section "Logging floor drying" on page 57. Chapter 8 | Control - Menus NIBE F470...
9 Service Maintenance NOTE F470 must be serviced once a year by compet- ent and qualified personnel, such as a NIBE a CLEANING THE OVERFLOW CUP/FLOOR service engineer or other qualified professional. DRAIN When replacing components on F470 only re- Regularly check that the overflow cup and any floor placement parts from NIBE may be used.
(MA1to "manual mode" and then turning the shunt SAFETY VALVES lever to the desired position. F470 has three safety valves, two for the water heater and one for the climate system. The function of the safety valves must be checked reg- ularly.
Page 55
HELPING THE CIRCULATION PUMP TO 12.51 2.399 10.00 2.245 START 8.045 2.083 The circulation pump in F470 has an automatic start help 6.514 1.916 function. If necessary the pump can be started manually. 5.306 1.752 In such cases, take the following action: 4.348 1.587...
Page 56
OK button you will return to the previous choose another file page (menu 7.1) where you can choose to start the up- date. This allows you to update the software in F470. Chapter 9 | Service NIBE F470...
Page 57
Via "save settings" you save the menu settings to the Here you can choose how current measurement values USB memory in order to restore them later or to copy from F470 should be saved onto a log file on the USB the settings to another F470. memory.
10 Disturbances in comfort In most cases, F470 notes a malfunction (a malfunction aid mode “aid mode” is a type of emergency mode. can lead to disruption in comfort) and indicates this with This means that the heat pump produces heat and/or alarms, and instructions for action, in the display.
Page 59
• The ventilation is not adjusted. thermostats. – Order/implement ventilation adjustment. • F470 in incorrect operating mode. • Exhaust air device blocked or throttled down too – Enter menu 4.2. If mode "auto" is selected, select a much.
Page 60
– F470 does not call on heating or hot water. – The heat pump defrosts. • Compressor blocked due to the temperature condi- tions. – Wait until the temperature is within the product’s working range. • Minimum time between compressor starts has not been reached.
The room unit is an accessory that allows the control and for anti-freeze and/or external heating medium pump. monitoring of F470 to be carried out in a different part of Part no. 067 609 your home to where it is located.
Scale for efficiency class hot water: A+ to F. The value varies with the selected fan curve. For more detailed sound data, including sound to channels, visit nibe.co.uk. The value can vary with the room’s damping capacity. These values apply at a damping of 4 dB.
Page 64
Height incl. feet 2,100 - 2,125 Required ceiling height 2,170 Net weight Mass unit, filled with water Part No. 066 053 A20(12) exhaust air flow 42 l/s (150 m /h). Comfort mode, normal Chapter 12 | Technical data NIBE F470...
The reported efficiency of the package also takes the controller into account. If an external supplementary boiler or solar heating is added to the package, the overall efficiency of the package should be recalculated. NIBE F470 Chapter 12 | Technical data...
Page 66
Daily energy consumption 5.92 Daily fuel consumption elec fuel Annual energy consumption 1,299 Annual fuel consumption Contact information NIBE Energy Systems – Box 14 – Hannabadsvägen 5 – 285 21 Markaryd – Sweden Chapter 12 | Technical data NIBE F470...
External connection options, 29 Control - Introduction, 43 Load monitor, 29 Control - Menus, 47 Miniature circuit-breaker, 25 Control - Introduction, 43 NIBE Uplink, 29 Display unit, 43 Optional connections, 29 Menu system, 44 Outdoor sensor, 26 Control knob, 43...
Page 74
Use the virtual keyboard, 46 Scroll through the windows, 46 Miniature circuit-breaker, 25 Selecting menu, 45 Selecting options, 45 Serial number, 9 NIBE Uplink, 29 Service, 53 Service actions, 54 OK button, 43 Service actions, 54 Operation, 45 Cleaning the water heater, 54...
Page 75
Temperature limiter, compressor, 25 Resetting, 25 Temperature sensor data, 55 The heat pump design, 14 Transport, 12 Troubleshooting, 58 USB service outlet, 56 Use the virtual keyboard, 46 Venting the climate system, 33 Warranty information, 10 NIBE F470 Item register...
Page 76
EXHAUST AIR HEAT PUMP COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the heat pump and associated equipment as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
Page 77
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
Page 78
Service Record It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Page 80
WS version: a818 (working edition) Publish date: 2020-09-04 09:41 This manual is a publication from NIBE Energy Systems. All product illustrations, facts and data are based on the available information at the time of the publication’s approval. NIBE Energy Systems makes reservations for any factual or printing errors in this manual.